LAN 900 (S/STP Pimf)
LAN 900 (S/STP Pimf)
Data Transmission Cable for Local Networks with Pair Wise Screening and Overall Shielding Category 7
Application:
In the horizontal wiring as an installation cable for the transfer in cable canals as well as in pipes within telecommunication installations and data systems. Area of application: ISDA, B-ISDA, IEEE 802.3 10 Base T Ethernet, IEEE 802.3 100 Base T Ethernet, IEEE 802.5 Token Ring CCDI (FDDI at Cu), Gigabit-Ethernet, ATM, DQDB, Video
Construction:
1 ..... solid bare copper, Ø 0,57 mm
2 ..... core insulation of foam-skin polyethylene
3 ..... pair wise screen of plastic laminated aluminium foil with a tinned drain wire Ø 0,4
4 ..... wide-meshed bare copper braiding
5 ..... outer sheath of polyvinylchloride (PVC) yellow or halogen-free polymer compound orange
Standards:
EN 50288-4-1
IEC 332-1, IEC 754-2 , IEC 1034-2
IEC 708-1 (core identification)
Technical data:
Temperature range | moved | 0°C till +60°C | |
Loop impedance | [Ohm/100 m] | 14,5 | |
Capacity | max. | [nF/km] | 50 |
Nom. Velocity of propagation | NVP nom. | 77 | |
Attenuation | 1-100 MHz | [Ohm] | 100,0 +/- 25 |
Coupling resistance | 1-100 MHz | [mOhm/m] | 10 |
Capacity coupling (f=800 Hz) | K<100 | [pF/100 m] | 150 |
Insulation resistance | [GOhm/m] | >5 | |
Test voltage at 50 Hz | [VAC] | 700 | |
Bending radius | under tension | 8,0 x Ø | |
no tension | 4,0 x Ø |
Number of pairs and nominal dimensions AWG Nr. | Copper figure kg/km | Overall diameter appr. mm | Calorific potential kWh/m | Tractive force N | Weight appr. kg/km | |||||
---|---|---|---|---|---|---|---|---|---|---|
4 x 2 x AWG 23 PVC | 44 | 8 | 0,17 | 190 | 74 | |||||
4 x 2 x AWG 23 FRNC | 44 | 8 | 0,16 | 190 | 74 | |||||
2 x(4 x 2x AWG 23) PVC | 88 | 16 | 0,35 | 380 | 148 | |||||
2 x(4 x 2x AWG 23) FRNC | 88 | 16 | 0,32 | 380 | 148 |