High-voltage cables 3,6-30 kV

Technical data:

Nominal voltage Uo/U[V]3600 / 6000 volt
Test voltage[V]AC11000
Temperature rangein motion -5°C till +70°C
fixed-20°C till +70°C
Operating temperatureshort circuit°C160
Short circuit timemax.[sec]5
Bending radiusin motion x diameter15
FlammabilitystandardEN 60332-1-2

Application:

To be laid directly in ground, in water, outdoors, indoors and in cable ducts if increased mechanical protection is required or if greater tensile stresses are to be expected during installation and operation.

Technical data:

Nominal voltage Uo/U[V]6000 / 10000 volt
Test voltage[V]AC21000
Temperature rangein motion -5°C till +70°C
fixed-20°C till +70°C
Operating temperatureshort circuit°C250
Short circuit timemax.[sec]5
Bending radiusmin.x diameter15
FlammabilitystandardEN 60332-1-2

Application:

To be laid directly in ground, water, outdoors, indoors and in cable ducts e.g. in industrial and switchboard plants.

Technical data:

Test voltage 6 / 10 kV[kV]21 / 5 min.
12 / 20 kV[kV]42 / 5 min.
18 / 30 kV[kV]63 / 5 min.
Temperature rangein motion -5°C till +70°C
fixed-20°C till +70°C
Operating temperatureshort circuit°C250
Short circuit timemax.[sec]5
Bending radiusmin.x diameter15
FlammabilitystandardEN 60332-1-2

Application:

To be laid directly in ground, outdoors, indoors and in cable ducts.

Technical data:

Test voltage 6 / 10 kV[kV]21 / 5 min.
12 / 20 kV[kV]42 / 5 min.
18 / 30 kV[kV]63 / 5 min.
Temperature rangein motion -5°C till +70°C
fixed-20°C till +70°C
Operating temperatureshort circuit°C250
Short circuit timemax.[sec]5
Bending radiusmin.x diameter15
FlammabilitystandardEN 60332-1-2

Application:

To be laid directly in ground, outdoors, indoors and in cable ducts.

Technical data:

Test voltage 6 / 10 kV[kV]21 / 5 min.
12 / 20 kV[kV]42 / 5 min.
18 / 30 kV[kV]63 / 5 min.
Temperature rangein motion -5°C till +70°C
fixed-20°C till +70°C
Operating temperatureshort circuit°C250
Short circuit timemax.[sec]5
Bending radiusmin.x diameter15
FlammabilitystandardEN 60332-1-2

Application:

To be laid directly in ground, outdoors, indoors and in cable ducts.

Technical data:

Test voltage 6 / 10 kV[kV]21 / 5 min.
12 / 20 kV[kV]42 / 5 min.
18 / 30 kV[kV]63 / 5 min.
Temperature rangein motion-20°C till +90°C
fixed-20°C till +90°C
Operating temperatureshort circuit°C250
Short circuit timemax.[sec]5
Bending radiusmin.x diameter15
FlammabilitystandardEN 60332-1-2

Application:

To be laid directly in ground, outdoors, indoors and in cable ducts.

Technical data:

Test voltage 6 / 10 kV[kV]21 / 5 min.
12 / 20 kV[kV]42 / 5 min.
18 / 30 kV[kV]63 / 5 min.
Temperature rangein motion-20°C till +90°C
fixed-20°C till +90°C
Operating temperatureshort circuit°C250
Short circuit timemax.[sec]5
Bending radiusmin.x diameter15
FlammabilitystandardEN 60332-1-2

Application:

To be laid directly in ground, outdoors, indoors and in cable ducts.

Technical data:

Test voltage 6 / 10 kV[kV]21 / 5 min.
12 / 20 kV[kV]42 / 5 min.
18 / 30 kV[kV]63 / 5 min.
Temperature rangein motion-20°C till +90°C
fixed-20°C till +90°C
Operating temperatureshort circuit°C250
Short circuit timemax.[sec]5
Bending radiusmin.x diameter15
FlammabilitystandardEN 60332-1-2

Application:

To be laid directly in ground, outdoors, indoors and in cable ducts.

Technical data:

Test voltage 6 / 10 kV[kV]21 / 5 min.
12 / 20 kV[kV]42 / 5 min.
18 / 30 kV[kV]63 / 5 min.
Temperature rangein motion-20°C till +90°C
fixed-20°C till +90°C
Operating temperatureshort circuit°C250
Short circuit timemax.[sec]5
Bending radiusmin.x diameter15
FlammabilitystandardEN 50265-2-1

Application:

To be laid directly in ground, in water, outdoors, indoors and in cable ducts.

Technical data:

Test voltage 6 / 10 kV[kV]21 / 5 min.
12 / 20 kV[kV]42 / 5 min.
18 / 30 kV[kV]63 / 5 min.
Temperature rangein motion-20°C till +90°C
fixed-20°C till +90°C
Operating temperatureshort circuit°C250
Short circuit timemax.[sec]5
Bending radiusmin.x diameter15
FlammabilitystandardEN 50265-2-1

Application:

To be laid directly in ground, in water, outdoors, indoors and in cable ducts.

Technical data:

Test voltage 6 / 10 kV[kV]21 / 5 min.
12 / 20 kV[kV]42 / 5 min.
18 / 30 kV[kV]63 / 5 min.
Temperature rangein motion-20°C till +90°C
fixed-20°C till +90°C
Operating temperatureshort circuit°C250
Short circuit timemax.[sec]5
Bending radiusmin.x diameter15
FlammabilitystandardEN 50265-2-1

Application:

To be laid directly in ground, in water, outdoors, indoors and in cable ducts.

Technical data:

Test voltage 6 / 10 kV[kV]21 / 5 min.
12 / 20 kV[kV]42 / 5 min.
18 / 30 kV[kV]63 / 5 min.
Temperature rangein motion -5°C till +70°C
fixed-20°C till +70°C
Operating temperatureshort circuit°C250
Short circuit timemax.[sec]5
Bending radiusmin.x diameter15
FlammabilitystandardEN 60332-1-2

Application:

To be laid directly in ground, outdoors, indoors and in cable ducts.

Technical data:

Test voltage 6 / 10 kV[kV]21 / 5 min.
12 / 20 kV[kV]42 / 5 min.
18 / 30 kV[kV]63 / 5 min.
Temperature rangein motion -5°C till +70°C
fixed-20°C till +70°C
Operating temperatureshort circuit°C250
Short circuit timemax.[sec]5
Bending radiusmin.x diameter15
FlammabilitystandardEN 60332-1-2

Application:

To be laid directly in ground, outdoors, indoors and in cable ducts.

Technical data:

Test voltage 6 / 10 kV[kV]21 / 5 min.
12 / 20 kV[kV]42 / 5 min.
18 / 30 kV[kV]63 / 5 min.
Temperature rangein motion -5°C till +70°C
fixed-20°C till +70°C
Operating temperatureshort circuit°C250
Short circuit timemax.[sec]5
Bending radiusmin.x diameter15
FlammabilitystandardEN 60332-1-2

Application:

To be laid directly in ground, outdoors, indoors and in cable ducts.

Technical data:

Test voltage 6 / 10 kV[kV]21 / 5 min.
12 / 20 kV[kV]42 / 5 min.
18 / 30 kV[kV]63 / 5 min.
Temperature rangein motion -5°C till +70°C
fixed-20°C till +70°C
Operating temperatureshort circuit°C250
Short circuit timemax.[sec]5
Bending radiusmin.x diameter15
FlammabilitystandardEN 60332-1-2

Application:

To be laid directly in ground, outdoors, indoors and in cable ducts.

Technical data:

Test voltage 6 / 10 kV[kV]21 / 5 min.
12 / 20 kV[kV]42 / 5 min.
18 / 30 kV[kV]63 / 5 min.
Temperature rangein motion -5°C till +70°C
fixed-20°C till +70°C
Operating temperatureshort circuit°C250
Short circuit timemax.[sec]5
Bending radiusmin.x diameter15
FlammabilitystandardEN 60332-1-2

Application:

To be laid directly in ground, outdoors, indoors and in cable ducts.

Technical data:

Test voltage 6 / 10 kV[kV]21 / 5 min.
12 / 20 kV[kV]42 / 5 min.
18 / 30 kV[kV]63 / 5 min.
Temperature rangein motion -5°C till +70°C
fixed-20°C till +70°C
Operating temperatureshort circuit°C250
Short circuit timemax.[sec]5
Bending radiusmin.x diameter15
FlammabilitystandardEN 60332-1-2

Application:

To be laid directly in ground, outdoors, indoors and in cable ducts.

Technical data:

Test voltage 6 / 10 kV[kV]21 / 5 min.
12 / 20 kV[kV]42 / 5 min.
18 / 30 kV[kV]63 / 5 min.
Temperature rangein motion -5°C till +90°C
fixed-20°C till +90°C
Operating temperatureshort circuit°C250
Short circuit timemax.[sec]5
Bending radiusmin.x diameter15
FlammabilitystandardEN 60332-1-2

Application:

To be laid directly in ground, outdoors, indoors and in cable ducts.

Technical data:

Test voltage 6 / 10 kV[kV]21 / 5 min.
12 / 20 kV[kV]42 / 5 min.
18 / 30 kV[kV]63 / 5 min.
Temperature rangein motion -5°C till +90°C
fixed-20°C till +90°C
Operating temperatureshort circuit°C250
Short circuit timemax.[sec]5
Bending radiusmin.x diameter15
FlammabilitystandardEN 60332-1-2

Application:

To be laid directly in ground, outdoors, indoors and in cable ducts.

Technical data:

Test voltage 6 / 10 kV[kV]21 / 5 min.
12 / 20 kV[kV]42 / 5 min.
18 / 30 kV[kV]63 / 5 min.
Temperature rangein motion -5°C till +90°C
fixed-20°C till +90°C
Operating temperatureshort circuit°C250
Short circuit timemax.[sec]5
Bending radiusmin.x diameter15
FlammabilitystandardEN 60332-1-2

Application:

To be laid directly in ground, outdoors, indoors and in cable ducts.