Halogen-free cables and flame-resistant cables

Technical data:

Nominal voltage Uo/U[V]450 / 750 volt
Test voltage[V]AC2500
Temperature rangein motion+5°C till +90°C
Operating temperatureshort circuit°C250
Short circuit timemax.[sec]5
Bending radiusone time / fixedx diameter6
FlammabilitystandardEN 60332-1
IEC 60332-1

Application:

For the internal wiring of switching systems, equipment and lights as well as for domestic installations, however, not for outdoor use.

Technical data:

Nominal voltage Uo/U[V]300 / 500 volt
Test voltage[V]AC2000
Temperature rangein motion+5°C till +90°C
Operating temperatureshort circuit°C250
Short circuit timemax.[sec]5
Bending radiusone time / fixedx diameter6
FlammabilitystandardEN 60332-1
IEC 60332-1

Application:

For fixed installations in devices and in or on lights, as well as for the house installation, especially for uses by their one low creation is demanded of smoke and corrosive gases in the fire case, however not outside.

Technical data:

Nominal voltage Uo/U[V]450 / 750 volt
Test voltage[V]AC2500
Temperature rangeone time / fixed+5°C till +90°C
Operating temperatureshort circuit°C250
Short circuit timemax.[sec]5
Bending radiusone time / fixedx diameter6
FlammabilitystandardEN 60332-1
IEC 60332-1

Application:

For the installation in electrical conduit on or under plaster or in similar closed systems especially for applications where there is a requirement for low smoke and corrosive gas creation in the event of fire, however not outside.

Technical data:

Nominal voltage Uo/U[V]300 / 500 volt
Test voltage[V]AC2000
Temperature rangein motion+5°C till +70°C
Operating temperatureshort circuit°C160
Short circuit timemax.[sec]5
Bending radiusin motionx diameter12
FlammabilitystandardEN 50266-2-4
EN 60332-1
IEC 60332-3 Kat.C

Application:

To be installed in buildings or industrial plants where many people and goods are concentrated. As they don't develop corrosive and halogen gases under the impact of fire, and the smoke and fume generation is also minimal, the damage caused is much smaller. They are destined for the installation on, in and under the wall-surface in dry, humid and wet locations as well as in brickwork or outdoors (when protected), but not directly into the earth.

Technical data:

Nominal voltage Uo/U[V]300 / 500 volt
Test voltage[V]AC2000
Temperature rangein motion-15°C till +70°C
Operating temperatureshort circuit°C150
Short circuit timemax.[sec]5
Bending radiusin motionx diameter15
FlammabilitystandardEN 50266-2-4
EN 60332-1
IEC 60332-3 Kat.C

Application:

For installations in dry, humid and wet locations, but not outdoors. These cables are used for fix or for flexible applications - but not with high tensile load or for forced bending.

Technical data:

Nominal voltage Uo/U[V]300 / 500 volt
Test voltage[V]AC2000
Temperature rangein motion-5°C till +70°C
Operating temperatureshort circuit°C150
Short circuit timemax.[sec]5
Bending radiusin motionx diameter15
FlammabilitystandardEN 50266-2-4
EN 60332-1
IEC 60332-3 Kat.C

Application:

For installations in dry, humid and wet locations but not outdoors. These cables are used for fix or for flexible applications - but not with high tensile load and for forced bending. Suitable as a signal and impulse cable in the control, measuring and signal technology. The copper braiding optimises protection against external interferences, like electromagnetic fields and stray frequencies.

Technical data:

Nominal voltage Uo/U[V]600 / 1000 volt
Test voltage[V]AC4000
Temperature rangein motion-5°C till +90°C
Operating temperatureshort circuit°C250
Short circuit timemax.[sec]5
Bending radiussingle-core stylex diameter15
multi-core stylex diameter12
FlammabilitystandardEN 50266-2-4
EN 60332-1
IEC 60332-3 Kat.C

Application:

Safety cables are used in all locations where a high degree of protection against fire and fire-damage has to be provided for human life and equipment and are, therefore, subject to high security requirements. These cables may be used indoors and outdoors. They may not be installed directly into the ground and into the water. This cable conforms to Safety Class II standards.

Technical data:

Nominal voltage Uo/U[V]600 / 1000 volt
Test voltage[V]AC4000
Temperature rangein motion-5°C till +90°C
Operating temperatureshort circuit°C250
Short circuit timemax.[sec]5
Bending radiusmin.x diameter12
FlammabilitystandardEN 50266-2-4
EN 60332-1
IEC 60332-3 Kat.C

Application:

Safety cables are used in all locations where a high degree of protection against fire and fire-damage has to be provided for human life and equipment and are, therefore, subject to high security requirements. These cables may be used indoors and outdoors. They may not be installed directly into the ground and into the water. This cable conforms to Safety Class II standards.

Technical data:

Operating peak voltage[V]300 volt
Temperature rangein motion -5°C till +50°C
fixed-30°C till +70°C
Bending radiusin motion x diameter7,5
FlammabilitystandardEN 50266-2-4
IEC 60332-3 Kat.C

Application:

These installation cables are suitable for fixed installations in telecommunication and are to be used in locations with fire hazard to reduce damage in case of fire.

Technical data:

Operating peak voltage[V]300 volt
Temperature rangein motion -5°C till +50°C
fixed-30°C till +70°C
Bending radiusin motion x diameter7,5
FlammabilitystandardEN 50266-2-4
IEC 60332-3 Kat.C

Application:

Suitable for fixed installations in telecommunication and are to be used in locations with fire hazard to reduce damage in case of fire.

Technical data:

Operating peak voltage[V]300 volt
Temperature rangein motion-5°C till +50°C
Conductor resistancemax.[Ohm/km]73,2
Insulation resistancemin.[MOhm/km]100
Mutal capacitanceat 800 Hz[nF] max.100
Test voltagecore / core[KV] 5min.1
Core and Screen on conductorsurface[KV] 1min.4
FlammabilitystandardEN 50266-2-4
IEC 60332-1

Application:

For the installation on and under plaster in dry, humid and wet rooms as wellas outside (by protected installation) in Strongly and weak streamarrangements, as BUS cable as well as as a MSR cable in strong streamarrangements. The transference of measuring values, the application in theprocess data processing as well as the use in the area of the tax technologyand control technology are the main areas of application of this cable.

Technical data:

Nominal voltage Uo/U[V]600 / 1000 volt
Test voltage[V]AC4000
Temperature rangein motion-5°C till +90°C
Operating temperatureshort circuit°C250
Short circuit timemax.[sec]5
Bending radiussingle-core stylex diameter15
multi-core stylex diameter12
FlammabilitystandardEN 50266-2-4
IEC 60332-3 Kat.C
More types on enquiry

Application:

Safety cables are used in all locations where a high degree of protectionagainst fire and fire-damage has to be provided for human life and equipmentand are, therefore, subject to high security requirements. These cables may beused indoors and outdoors. They may not be installed directly into the groundand into the water. This cable conforms with Safety Class II standards.Functional integrity of 30 minutes and insulation integrity of 180 minutes.

Technical data:

Nominal voltage Uo/U[V]600 / 1000 volt
Test voltage[V]AC4000
Temperature rangein motion-5°C till +90°C
Operating temperatureshort circuit°C250
Short circuit timemax.[sec]5
Bending radiusin motionx diameter12
FlammabilitystandardEN 50266-2-4
IEC 60332-3 Kat.C
More types on enquiry

Application:

Safety cables are used in all locations where a high degree of protectionagainst fire and fire-damage has to be provided for human life and equipmentand are, therefore, subject to high security requirements. These cables may beused indoors and outdoors. They may not be installed directly into the groundand into the water. Functional integrity of 30 minutes and insulation integrity of180 minutes.

Technical data:

Operating peak voltage[V]225 volt
Temperature rangein motion -5°C till +50°C
one time / fixed-30°C till +70°C
Bending radiusin motionx diameter7,5
FlammabilitystandardEN 50266-2-4
EN 60332-1
IEC 60332-3 Kat.C
Insulation resistancemin.[MOhm/km]100
Mutal capacitance[Ohm/km]73,2
max.[nF/km]120
Capacitance unbalance 100mmax.[pF]200

Application:

Suitable for fixed installations in telecommunication. They are to be used inlocations with fire hazard and where insulation integrity of at least 180 minutesand circuit integrity of at least 30 minutes are required.

Technical data:

Operating peak voltage[V]225 volt
Temperature rangein motion -5°C till +50°C
fixed-30°C till +70°C
Bending radiusin motionx diameter7,5
FlammabilitystandardEN 50266-2-4
EN 60332-1
IEC 60332-3 Kat.C
Insulation resistancemin.[MOhm/km]100
Mutal capacitance[Ohm/km]73,2
max.[nF/km]120
Capacitance unbalance 100mmax.[pF]200

Application:

Suitable for fixed installations in fire detection circuits. They are to be used inlocations with fire hazard and where an insulation integrity of at least 180minutes and a circuit integrity of at least 30 minutes are required.

Technical data:

Nominal voltage Uo/U[V]600 / 1000 volt
Test voltage[V]AC4000
Temperature rangein motion-5°C till +90°C
Operating temperatureshort circuit°C250
Short circuit timemax.[sec]5
Bending radiussingle-core style x diameter15
multi-core stylex diameter12
FlammabilitystandardEN 50266-2-4
IEC 60332-3 Kat.C
More types on enquiry

Application:

Safety cables are used in all locations where a high degree of protection against fire and fire-damage has to be provided for human life and equipment and are, therefore, subject to high security requirements. These cables may beused indoors and outdoors. They may not be installed directly into the groundand into the water. Functional integrity of 90 minutes and insulation integrity of 180 minutes.

Technical data:

Nominal voltage Uo/U[V]600 / 1000 volt
Test voltage[V]AC4000
Temperature rangein motion-5°C till +90°C
Operating temperatureshort circuit°C250
Short circuit timemax.[sec]5
Bending radiusin motionx diameter12
FlammabilitystandardEN 50266-2-4
IEC 60332-3 Kat.C
More types on enquiry

Application:

Safety cables are used in all locations where a high degree of protection against fire and fire-damage has to be provided for human life and equipment and are, therefore, subject to high security requirements. These cables may beused indoors and outdoors. They may not be installed directly into the ground and into the water. Functional integrity of 90 minutes and insulation integrity of 180 minutes.

Technical data:

Operating peak voltage[V]225 volt
Temperature rangein motion -5°C till +50°C
one time / fixed-30°C till +70°C
Bending radiusin motionx diameter7,5
FlammabilitystandardEN 50266-2-4
EN 60332-1
IEC 60332-3 Kat.C
Insulation resistancemin.[MOhm/km]100
Mutal capacitance[Ohm/km]73,2
max.[nF/km]120
Capacitance unbalance 100mmax.[pF]200

Application:

Suitable for fixed installations in telecommunication. They are to be used in locations with fire hazard and where insulation integrity of at least 180 minutes and circuit integrity of at least 90 minutes are required.

Technical data:

Operating peak voltage[V]225 volt
Temperature rangein motion -5°C till +50°C
one time / fixed-30°C till +70°C
Bending radiusin motionx diameter7,5
FlammabilitystandardEN 50266-2-4
EN 60332-1
IEC 60332-3 Kat.C
Insulation resistancemin.[MOhm/km]100
Mutal capacitance[Ohm/km]73,2
max.[nF/km]120
Capacitance unbalance 100mmax.[pF]200

Application:

Suitable for fixed installations in telecommunication. They are to be used in locations with fire hazard and where insulation integrity of at least 180 minutes and circuit integrity of at least 90 minutes are required.