INTERBUS
INTERBUS
Application:
The circuit can connect different components within automation devices. The twisted cores are also the basic element. Because all bus components are connected about that, costly parallel wiring can be avoided.
Construction:
1 ..... fine-stranded bare copper
2 ..... core insulation of polyethylene (PE)
3 ..... layer of plastic foil
4 ..... wide-meshed bare copper braiding
5 ..... outer sheath of polyvinylchloride (PVC), magenta
Information:
For other types and standards please send us an inquiry.
Standards:
according to DIN 47100 or factory standard (core identification)
Technical data:
Temperature range | in motion | -5°C till +60°C | |
one time / fixed | 0°C till +50°C | ||
Conductor resistance | max. | [Ohm/km] | 83 |
Impendance | 1-100 MHz | [Ohm]+-15% | 100 |
Mutal capacitance | nom. | [nF] max. | 50 |
Attenuation | 1,0 MHz | [dB/100 m] | 2,7 |
4,0 MHz | [dB/100 m] | 5,2 | |
10,0 MHz | [dB/100 m] | 8,4 | |
16,0 MHz | [dB/100 m] | 11,2 |
Number of pairs and nominal cross section mm2 | Copper figure kg/km | Overall diameter appr. mm | Weight appr. kg/km | |||
---|---|---|---|---|---|---|
3 x 2 x 0,22 | 39 | 7,4 | 70 | |||
3 x 2 x 0,25 | 40 | 7,9 | 75 |