J-Y(ST)Y EIB

J-Y(ST)Y EIB

MSR Installation Cable with Static Screen European Installation Bus

Application:

The installation in, on and under the wall surface, in dry, humid and wet locations as well as outdoors (if protected) is admissible. As BUS-installation cable (EIB-installation bus) it may be used in HV and LV installations, as control and instrumentation cable (MSR-cable) in HV installations. Suitable for the transmission of measuring data, for the installation in the processing and for the application in the field of the control technology.

Construction:

1 ..... solid bare copper
2 ..... core insulation of polyvinylchloride (PVC)
3 ..... layer of plastic foil
4 ..... static screen of plastic coated aluminium foil with drain wire
5 ..... outer sheath of polyvinylchloride (PVC) green or grey

Information:

Cores twisted to starquads. (see technical attachment)

Standards:

DIN VDE 0815 (core identification)
DIN EN 60228 Class 1 (construction)
EIBA spezification

Technical data:

Operating peak voltage Uo/U[V]300
Temperature rangein motion -5°C till +50°C
one time / fixed-30°C till +70°C
Conductor resistancemax.[Ohm/km]73,2
Insulation resistancemin.[MOhm/km]100
Mutal capacitanceat 800 Hz[nF] max.100
Test voltagecore / core[KV] 5 min.1
Core and Screen on
Conductorsurface[KV] 1 min.4
Bending radiusx diameter15
Number of pairs
and nominal
cross section
mm2
Copper
figure

kg/km
Overall
diameter
appr.
mm
Weight

appr.
kg/km
2 x 2 x 0,8216,660
This website uses cookies to provide services, personalize ads, and analyzing visitor. By using this site you agree. More informations