YMT
YMT
PVC Cable with Steel Carrier
Application:
Usable as a self-supporting circuit on free power mains, in accordance with applicable regulation. They may not be installed directly into the ground.
Construction:
1 ..... bare copper, solid (RE) or stranded (RM)
2 ..... polyvinylchloride (PVC) insulation
3 ..... carrier cable steel-reinforced, stranded
4 ..... bedding
5 ..... polyvinylchloride (PVC) outer sheath, black
Information:
The minimum value for the breaking force of the supporting
element amounts to:
6.000 N u 3 x 2,5 and 5 x 2,5 mm²
10.500 N u 4 x 10 and 4 x 16 mm²
Information according to DIN VDE 0250-206
Standards:
according to ÖVE K41
DIN 57250 part 206
VDE 0250-206
DIN EN 60228 class 1 and 2 (construction)
HD 308 S2 (core identification)
Technical data:
Nominal voltage Uo/U | [V] | 300 / 500 volt | |
Test voltage | [V]AC | 4000 | |
Temperature range | in motion | +5°C till +70°C | |
fixed | -40°C till +70°C | ||
Operating temperature | short circuit | °C | 160 |
Short circuit time | max. | [sec] | 5 |
Bending radius | min. | x diameter | 4 |
Flammability | standard | EN 60332-1-2 |
Number of cores and nominal cross section mm2 | Copper figure kg/km | Overall measures appr. mm | Weight appr. kg/km | ||
---|---|---|---|---|---|
3 x 2,5 RE | 75 | 12,5 x 20,5 | 190,0 | ||
4 x 10 RM | 400 | 19,0 x 28,0 | 960,0 | ||
4 x 16 RM | 640 | 22,0 x 32,0 | 1.320,0 | ||
5 x 2,5 RE | 125 | 14,5 x 23,0 | 361,0 |