(N)YM(ST)-J
(N)YM(ST)-J
PVC Sheathed Wire with Screen Bio Wire
Application:
Suitable where effective limitation of electro-magnetic interference fields is necessary, for installations in dry, humid and wet locations. Not suitable for laying directly open-air or in concrete. Not suitable in areas with explosion Hazard.
Construction:
1 ..... solid bare copper
2 ..... polyvinylchloride (PVC) insulation
3 ..... screen of plastic coated aluminium tape with tinned drain wire
4 ..... polyvinylchloride (PVC) outer sheath, grey
Standards:
adapted to DIN VDE 250-204
DIN EN 60228 Class 1 (construction)
HD 308 S2 (core identification)
Technical data:
Nominal voltage Uo/U | [V] | 300 / 500 volt | |
Test voltage | [V]AC | 2000 | |
Temperature range | in motion | +5°C till +70°C | |
Operating temperature | short circuit | °C | 160 |
Short circuit time | max. | [sec] | 5 |
Flammability | standard | EN 60332-1-2 |
Number of cores and nominal cross section mm2 | Copper figure kg/km | Cond. construction (appr. value) mm | Overall diameter appr. mm | Calorific potential kwh / m | Weight appr. kg/km | ||||
---|---|---|---|---|---|---|---|---|---|
3 x 1,5 / 1,5 | 55 | 1 x 1,38 | 10,5 | 0,44 | 140 | ||||
4 x 1,5 / 1,5 | 68 | 1 x 1,38 | 11,5 | 0,53 | 188 | ||||
5 x 1,5 / 1,5 | 83 | 1 x 1,38 | 12,0 | 0,58 | 216 | ||||
7 x 1,5 / 1,5 | 113 | 1 x 1,38 | 13,0 | 0,67 | 263 | ||||
3 x 2,5 / 1,5 | 83 | 1 x 1,78 | 12,0 | 0,58 | 214 | ||||
5 x 2,5 / 1,5 | 133 | 1 x 1,78 | 13,5 | 0,75 | 300 |