JE-H(ST)H E90 …Bd

JE-H(ST)H E90 …Bd

Halogen-Free and Flame Retardant Installaion Cable for Industrial Electronics with Circuit Integrity of 90 Minutes

Application:

Suitable for fixed installations in telecommunication. They are to be used in locations with fire hazard and where insulation integrity of at least 180 minutes and circuit integrity of at least 90 minutes are required.

Construction:

1 ..... solid bare copper
2 ..... flame protective wrapping
3 ..... core insulation of halogen-free, cross-linked polymer (HI 1)
4 ..... core covering of foil
5 ..... halogen-free inner sheath
6 ..... static screen of plastic coated metal foil with a solid tinned drain wire 0,8 mm
7 ..... outer sheath of halogen-free polymer (HM 2), orange

Information:

These cables fulfil the conditions of the tests to insulation integrity according to DIN VDE 0472-814/ 8.83 about 180 min. and IEC Public. 331 first edition 1970 to circuit integrity about 30 min. to DIN 4102-12 according to VDE 0100-710 and 0100-718.

Standards:

DIN VDE 0815 (core identification)
DIN EN 60228 Class 1 (construction)
DIN VDE 0207-24

Technical data:

Operating peak voltage[V]225 volt
Temperature rangein motion -5°C till +50°C
one time / fixed-30°C till +70°C
Bending radiusin motionx diameter7,5
FlammabilitystandardEN 50266-2-4
EN 60332-1
IEC 60332-3 Kat.C
Insulation resistancemin.[MOhm/km]100
Mutal capacitance[Ohm/km]73,2
max.[nF/km]120
Capacitance unbalance 100mmax.[pF]200
Number of pairs
and nominal
conductor diameter
(mm)
Copper
figure

kg/km
Insulation
thickness

mm
Overall
diameter
appr.
mm
Calorific
potential

kWh/m
Weight

appr.
kg/km
2 x 2 x 0,8251,012,80,56177
4 x 2 x 0,8451,016,30,85284
8 x 2 x 0,8851,220,31,33447
12 x 2 x 0,81261,223,91,84615
16 x 2 x 0,81661,422,52,22756
20 x 2 x 0,82061,429,42,72921