H05Z-K

H05Z-K

Halogen-Free Single Core Wire

Application:

For fixed installations in devices and in or on lights, as well as for the house installation, especially for uses by their one low creation is demanded of smoke and corrosive gases in the fire case, however not outside.

Construction:

1 ..... fine-stranded tinned or bare copper
2 ..... core insulation of halogen-free, cross-linked
polyolefin copolymerisate (EI5)

Standards:

DIN VDE 0282-9
HD 22.9 S2+A1
DIN EN 60228 class 5 (construction)

Technical data:

Nominal voltage Uo/U[V]300 / 500 volt
Test voltage[V]AC2000
Temperature rangein motion+5°C till +90°C
Operating temperatureshort circuit°C250
Short circuit timemax.[sec]5
Bending radiusone time / fixedx diameter6
FlammabilitystandardEN 60332-1
IEC 60332-1
Number of cores and
nominal cross section

mm2
Colours


Copper
figure

kg/km
Overall
diameter
appr.
mm
Calorific
potential

kWh/m
Weight

appr.
kg/km
0,50sw/bl/br5,02,20,239
gg5,02,20,239
0,75sw/dbl/bl/br7,52,40,2612
gg/gr/or/rt7,52,40,2612
1,00sw/bl/br10,02,50,2915
gg/ws/or/rt10,02,50,2915
This website uses cookies to provide services, personalize ads, and analyzing visitor. By using this site you agree. More informations