H05Z-K
H05Z-K
Halogen-Free Single Core Wire
Application:
For fixed installations in devices and in or on lights, as well as for the house installation, especially for uses by their one low creation is demanded of smoke and corrosive gases in the fire case, however not outside.
Construction:
1 ..... fine-stranded tinned or bare copper
2 ..... core insulation of halogen-free, cross-linked
polyolefin copolymerisate (EI5)
Standards:
DIN VDE 0282-9
HD 22.9 S2+A1
DIN EN 60228 class 5 (construction)
Technical data:
Nominal voltage Uo/U | [V] | 300 / 500 volt | |
Test voltage | [V]AC | 2000 | |
Temperature range | in motion | +5°C till +90°C | |
Operating temperature | short circuit | °C | 250 |
Short circuit time | max. | [sec] | 5 |
Bending radius | one time / fixed | x diameter | 6 |
Flammability | standard | EN 60332-1 | |
IEC 60332-1 |
Number of cores and nominal cross section mm2 | Colours | Copper figure kg/km | Overall diameter appr. mm | Calorific potential kWh/m | Weight appr. kg/km | |||||
---|---|---|---|---|---|---|---|---|---|---|
0,50 | sw/bl/br | 5,0 | 2,2 | 0,23 | 9 | |||||
gg | 5,0 | 2,2 | 0,23 | 9 | ||||||
0,75 | sw/dbl/bl/br | 7,5 | 2,4 | 0,26 | 12 | |||||
gg/gr/or/rt | 7,5 | 2,4 | 0,26 | 12 | ||||||
1,00 | sw/bl/br | 10,0 | 2,5 | 0,29 | 15 | |||||
gg/ws/or/rt | 10,0 | 2,5 | 0,29 | 15 |