J-H(ST)H BMK ...Bd

J-H(ST)H BMK ...Bd

Halogen-Free and Flame Retardant Fire Alarm Cable

Application:

Suitable for fixed installations in telecommunication and are to be used in locations with fire hazard to reduce damage in case of fire.

Construction:

1 ..... solid bare copper
2 ..... core insulation of halogen-free polymer (HI 2)
3 ..... wrapped in a plastic foil
4 ..... static screen of plastic coated aluminium foilwith drain wire 0,6mm or 0,8mm
5 ..... outer sheath of halogen-free polymer (HM 2)red with the marking "BRANDMELDECable" (fire alarm cable)

Information:

Cores twisted to star-quads, 5 quads a unit, unit to layers.Layer identification with coloured tapes.

Standards:

DIN VDE 0815 (core identification)
DIN EN 60228 Class 1 (construction)
DIN VDE 0207-24

Technical data:

Operating peak voltage[V]300 volt
Temperature rangein motion -5°C till +50°C
fixed-30°C till +70°C
Bending radiusin motion x diameter7,5
FlammabilitystandardEN 50266-2-4
IEC 60332-3 Kat.C
Number of pairs
and nominal
conductor diameter
(mm)
Copper
figure

kg/km
Insulation
thickness

mm
Overall
diameter
appr.
mm
Calorific
potential

kWh/m
Weight

appr.
kg/km
1 x 2 x 0,8111,06,50,1560
2 x 2 x 0,8251,06,80,2266
4 x 2 x 0,8411,09,90,37113
6 x 2 x 0,8621,010,40,43141
10 x 2 x 0,81021,212,20,60200
20 x 2 x 0,82031,415,50,95342
40 x 2 x 0,84041,420,81,80632
50 x 2 x 0,85051,622,72,05764
60 x 2 x 0,86061,624,92,48920
This website uses cookies to provide services, personalize ads, and analyzing visitor. By using this site you agree. More informations