H07Z-U
H07Z-U
Halogen-Free Single Core Wire
Application:
For the internal wiring of switching systems, equipment and lights as well as for domestic installations, however, not for outdoor use.
Construction:
1 ..... solid bare copper
2 ..... core insulation of halogen-free, cross-linked
polyolefin copolymerisate ( EI5)
Standards:
DIN VDE 0282-9
HD 22.9 S2+A1
DIN EN 60228 Class 1 (construction)
Technical data:
| Nominal voltage Uo/U | [V] | 450 / 750 volt | |
| Test voltage | [V]AC | 2500 | |
| Temperature range | in motion | +5°C till +90°C | |
| Operating temperature | short circuit | °C | 250 |
| Short circuit time | max. | [sec] | 5 |
| Bending radius | one time / fixed | x diameter | 6 |
| Flammability | standard | EN 60332-1 | |
| IEC 60332-1 |
| Number of cores and nominal cross section mm2 | Colours | Copper figure kg/km | Overall diameter appr. mm | Calorific potential kWh/m | Weight appr. kg/km | |||||
|---|---|---|---|---|---|---|---|---|---|---|
| 1,5 | sw/bl/br | 15 | 2,8 | 0,37 | 19 | |||||
| gg | 15 | 2,8 | 0,37 | 19 | ||||||
| 2,5 | sw/bl | 25 | 3,4 | 0,44 | 31 | |||||
| gg | 25 | 3,4 | 0,44 | 31 | ||||||