JE-H(ST)H E30 …Bd
JE-H(ST)H E30 …Bd
Halogen-Free and Flame Retardant Insallation Cablefor Industrial Electronics with Circuit Integrity of 30 Minutes
Application:
Suitable for fixed installations in telecommunication. They are to be used inlocations with fire hazard and where insulation integrity of at least 180 minutesand circuit integrity of at least 30 minutes are required.
Construction:
1 ..... solid bare copper
2 ..... core insulation of halogen-free, similar ceramicpolymer compound (HI 1), stranded to pairs
3 ..... layer of plastic foil
4 ..... static screen of plastic coated metal foil with asolid tinned drain wire 0,8mm
5 ..... outer sheath of halogen-free polymer (HM 4), orange
Information:
These cables fulfil the conditions of the tests to insulation integrity according toDIN VDE 0472-814/ 8.83 about 180 min. and IEC Public. 331 first edition 1970to circuit integrity about 30 min. to DIN 4102-12 according to VDE 0100-710and 0100-718.
Standards:
DIN VDE 0815 (core identification)
DIN EN 60228 Class 1 (construction)
DIN VDE 0207-24
Technical data:
Operating peak voltage | [V] | 225 volt | |
Temperature range | in motion | -5°C till +50°C | |
one time / fixed | -30°C till +70°C | ||
Bending radius | in motion | x diameter | 7,5 |
Flammability | standard | EN 50266-2-4 | |
EN 60332-1 | |||
IEC 60332-3 Kat.C | |||
Insulation resistance | min. | [MOhm/km] | 100 |
Mutal capacitance | [Ohm/km] | 73,2 | |
max. | [nF/km] | 120 | |
Capacitance unbalance 100m | max. | [pF] | 200 |
Number of pairs and nominal conductor diameter (mm) | Copper figure kg/km | Insulation thickness mm | Overall diameter appr. mm | Calorific potential kWh/m | Weight appr. kg/km | |||||
---|---|---|---|---|---|---|---|---|---|---|
2 x 2 x 0,8 | 25 | 1,0 | 6,6 | 0,13 | 61 | |||||
4 x 2 x 0,8 | 45 | 1,0 | 8,8 | 0,20 | 104 | |||||
8 x 2 x 0,8 | 85 | 1,2 | 12,8 | 0,34 | 218 | |||||
12 x 2 x 0,8 | 126 | 1,2 | 13,5 | 0,39 | 235 | |||||
20 x 2 x 0,8 | 206 | 1,4 | 16,1 | 0,53 | 367 | |||||
32 x 2 x 0,8 | 340 | 1,4 | 20,6 | 0,85 | 645 |