F-2YC2Y

F-2YC2Y

Plastic Insulated Telecommunication Cable for Local Networks

Application:

They are suitable for the installation into the earth, in conduits, cable ducts and are used as network cables in industrial and operational plants, mainly in lowfrequency installations.

Construction:

1 ..... solid bare copper Ø 0,6/0,8 mm
2 ..... core insulation of polyethylene (PE)
3 ..... static screen of copper tape
4 ..... outer sheath of polyethylene (PE), black

Information:

conductor loop resistance:
core Ø 0,6 mm ..... < 130,0 Ohm/km
core Ø 0,8 mm ..... < 73,2 Ohm/km
Cores twisted to star-quads.
Core colours: transparent (or black by the start quad), red, green, blue

Standards:

adapted to austrian telecom standa

Technical data:

Operating peak voltage[V]200 V eff. / 300 V
Test voltage at 50 Hzcore / core[V]AC500
core / screen[V]AC2000
Temperature rangein motion-20°C till +90°C
Bending radiusin motionx diameter15
Insulation resistancemin.[MOhm/km]10000
Mutal capacitancemax.[nF/km]55
Capacitance unbalance 100mmax.[pF]1500
Number of pairs
and nominal
conductor diameter
(mm)
Copper
figure

kg/km
Insulation
thickness

mm
Overall
diameter
appr.
mm
Weight

appr.
kg/km
2 x 2 x 0,631,51,88,678,0
6 x 2 x 0,670,01,810,1110,0
10 x 2 x 0,697,01,811,5150,0
20 x 2 x 0,6173,01,815,0250,0
30 x 2 x 0,6242,01,816,5320,0
40 x 2 x 0,6304,51,817,8400,0
50 x 2 x 0,6370,51,819,2480,0
60 x 2 x 0,6433,01,819,9550,0
100 x 2 x 0,6682,02,025,0865,0
2 x 2 x 0,850,01,88,395,0
6 x 2 x 0,8104,51,811,5150,0
10 x 2 x 0,8160,01,813,0205,0
20 x 2 x 0,8279,01,817,5360,0
30 x 2 x 0,8392,01,819,5485,0
40 x 2 x 0,8500,51,821,0605,0
50 x 2 x 0,8614,52,023,0732,0
60 x 2 x 0,8725,02,023,6865,0
100 x 2 x 0,81,161,02,033,01.390,0