A-2Y(L)2Y
A-2Y(L)2Y
Plastic Insulated Telecommunication Cable for Local Networks
Application:
Suitable for the installation into the earth, in conduits, cable ducts and are used as network cables in industrial and operational plants, mainly in LF-installations.
Construction:
1 ..... solid bare copper Ø 0,6/0,8 mm
2 ..... core insulation of polyethylene (PE)
3 ..... layer of plastic foil
4 ..... screen of plastic laminated aluminium foil
5 ..... outer sheath of polyethylene (PE), black
Information:
conductor loop resistance:
core Ø 0,6 mm ..... < 130,0 Ohm/km
core Ø 0,8 mm ..... < 73,2 Ohm/km
Cores twisted to star-quads.
Standards:
DIN VDE 0816 (core identification)
DIN EN 60228 class 1 (construction)
Technical data:
Operating peak voltage | [V] | 225 volt | |
Test voltage at 50 Hz | core / core | [V]AC | 500 |
core / screen | [V]AC | 2000 | |
Temperature range | in motion | -20°C till +50°C | |
one time / fixed | -20°C till +70°C | ||
Bending radius | in motion | x diameter | 15 |
Insulation resistance | min. | [MOhm/km] | 5000 |
Mutal capacitance | max. | [nF/km] | 52 |
Capacitance unbalance 100m | max. | [pF] | 800 |
Number of pairs and nominal conductor diameter (mm) | Copper figure kg/km | Insulation thickness mm | Overall diameter appr. mm | Weight appr. kg/km | ||||
---|---|---|---|---|---|---|---|---|
2 x 2 x 0,6 | 13 | 1,8 | 8,1 | 63 | ||||
6 x 2 x 0,6 | 36 | 1,8 | 9,3 | 86 | ||||
10 x 2 x 0,6 | 59 | 1,8 | 11,5 | 146 | ||||
20 x 2 x 0,6 | 115 | 1,8 | 15,2 | 239 | ||||
40 x 2 x 0,6 | 228 | 1,8 | 18,0 | 391 | ||||
50 x 2 x 0,6 | 285 | 1,8 | 19,4 | 469 | ||||
100 x 2 x 0,6 | 568 | 2,0 | 27,9 | 878 | ||||
2 x 2 x 0,8 | 22 | 1,8 | 8,6 | 74 | ||||
6 x 2 x 0,8 | 62 | 1,8 | 11,3 | 141 | ||||
10 x 2 x 0,8 | 103 | 1,8 | 13,2 | 203 | ||||
20 x 2 x 0,8 | 203 | 1,8 | 17,3 | 346 | ||||
40 x 2 x 0,8 | 404 | 2,0 | 20,7 | 590 | ||||
50 x 2 x 0,8 | 505 | 2,0 | 22,5 | 715 |