(N)YFGY

(N)YFGY

Three-Core PVC Insulated Cable with Flat Wire Amour

Application:

To be laid directly in ground, in water, outdoors, indoors and in cable ducts if increased mechanical protection is required or if greater tensile stresses are to be expected during installation and operation.

Construction:

1 ..... stranded bare copper
2 ..... core insulation of polyvinylchloride (PVC-DIV4)
3 ..... rubber core covering
4 ..... inner sheath z polyvinylchloridu (PVC-DMV5)
5 ..... armour of galvanised flat steel wires and counter helix
6 ..... outer sheath of polyvinylchloride (PVC), red

Standards:

DIN VDE 0271
DIN VDE 0276-603
DIN EN 60228 class 2 (construction)

Technical data:

Nominal voltage Uo/U[V]3600 / 6000 volt
Test voltage[V]AC11000
Temperature rangein motion -5°C till +70°C
fixed-20°C till +70°C
Operating temperatureshort circuit°C160
Short circuit timemax.[sec]5
Bending radiusin motion x diameter15
FlammabilitystandardEN 60332-1-2
Number of cores and
nominal cross section

mm2
Copper
figure

kg/km
Overall
diameter
appr.
mm
Weight

appr.
kg/km
Current
carrying
capacity ground
A
Current
carrying
capacity air
A
3 x 50 SM1.500,0413.520,0175165
3 x 70 SM2.100,0444.345,0220205
3 x 95 SM2.850,0475.330,0260250
3 x 120 SM3.600,0496.220,0295285
3 x 150 SM4.500,0527.120,0335325
3 x 185 SM5.550,0578.625,0370380
3 x 240 SM7.200,0599.885,0425430