N2XS2Y (18 / 30 kV)

N2XS2Y (18 / 30 kV)

XLPE Insulated Single-Core Cable with PE Outer Sheath

Application:

To be laid directly in ground, outdoors, indoors and in cable ducts.

Construction:

1 ..... stranded (RM) bare copper
2 ..... inner layer of semi-conducting material
3 ..... core insulation of cross-linked polyethylene
4 ..... outer layer of semi-conducting material
5 ..... screen of copper wires
6 ..... outer sheath of polyethylene (PE), black

Standards:

DIN VDE 0276-620
HD 620 S1: 1996
DIN EN 60228 class 2 (construction)

Technical data:

Test voltage 6 / 10 kV[kV]21 / 5 min.
12 / 20 kV[kV]42 / 5 min.
18 / 30 kV[kV]63 / 5 min.
Temperature rangein motion-20°C till +90°C
fixed-20°C till +90°C
Operating temperatureshort circuit°C250
Short circuit timemax.[sec]5
Bending radiusmin.x diameter15
FlammabilitystandardEN 60332-1-2
Number of cores and
nominal cross section

mm2
Copper
figure

kg/km
Overall
diameter
appr.
mm
Overall
diameter
max. value
appr. mm
Weight

appr.
kg/km
Current
carrying
capacity ground
A
Current
carrying
capacity air
A
1 x 50 RM/16690,033381.350,0225241
1 x 70 RM/16890,035401.600,0274299
1 x 95 RM/161.140,036411.900,0327363
1 x 120 RM/161.390,0288432.200,0371418
1 x 150 RM/251.795,044442.550,0414472
1 x 185 RM/252.145,056462.950,0466539
1 x 240 RM/252.695,043483.500,0539635
1 x 300 RM/253.295,046514.150,0606725
1 x 400 RM/354.410,049545.150,0680831
1 x 500 RM/355.410,052576.200,0765953
* trefoil touching arrangement
This website uses cookies to provide services, personalize ads, and analyzing visitor. By using this site you agree. More informations