NA2XS2Y (6 / 10 kV)
NA2XS2Y (6 / 10 kV)
XLPE Insulated Single-Core Cable with PE Outer Sheath
Application:
To be laid directly in ground, outdoors, indoors and in cable ducts.
Construction:
1 ..... stranded (RM) aluminium wires
2 ..... inner layer of semi-conducting material
3 ..... core insulation of cross-linked polyethylene
4 ..... outer layer of semi-conducting material
5 ..... screen of copper wires
6 ..... outer sheath of polyethylene (PE), black
Standards:
DIN VDE 0276-620
HD 620 S1: 1996
DIN EN 60228 class 2 (construction)
Technical data:
Test voltage | 6 / 10 kV | [kV] | 21 / 5 min. |
12 / 20 kV | [kV] | 42 / 5 min. | |
18 / 30 kV | [kV] | 63 / 5 min. | |
Temperature range | in motion | -5°C till +70°C | |
fixed | -20°C till +70°C | ||
Operating temperature | short circuit | °C | 250 |
Short circuit time | max. | [sec] | 5 |
Bending radius | min. | x diameter | 15 |
Flammability | standard | EN 60332-1-2 |
Number of cores and nominal cross section mm2 | Aluminium figure kg/km | Copper figure kg/km | Overall diameter appr. mm | Overall diameter max. value appr. mm | Weight appr. kg/km | Current carrying capacity ground A | Current carrying capacity air A | |||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
6 / 10 kV | ||||||||||||||
1 x 35 RM/16 | 103,0 | 190 | 23 | 28 | 600,0 | 145 | 153 | |||||||
1 x 50 RM/16 | 147,0 | 190 | 24 | 29 | 670,0 | 171 | 183 | |||||||
1 x 70 RM/16 | 206,0 | 190 | 26 | 31 | 770,0 | 208 | 228 | |||||||
1 x 95 RM/16 | 279,0 | 190 | 27 | 32 | 880,0 | 248 | 278 | |||||||
1 x 120 RM/16 | 353,0 | 190 | 29 | 34 | 950,0 | 283 | 321 | |||||||
1 x 150 RM/25 | 441,0 | 295 | 30 | 35 | 1.150,0 | 315 | 364 | |||||||
1 x 185 RM/25 | 544,0 | 295 | 32 | 37 | 1.250,0 | 357 | 418 | |||||||
1 x 240 RM/25 | 706,0 | 295 | 34 | 39 | 1.500,0 | 413 | 494 | |||||||
1 x 300 RM/25 | 882,0 | 295 | 36 | 41 | 1.700,0 | 466 | 568 | |||||||
1 x 400 RM/35 | 1.176,0 | 410 | 40 | 45 | 2.100,0 | 529 | 660 |