N2XSY (12 / 20 kV)
N2XSY (12 / 20 kV)
XLPE Insulated Single-Core Cable with PVC Outer Sheath
Application:
To be laid directly in ground, outdoors, indoors and in cable ducts.
Construction:
1 ..... stranded (RM) bare copper
2 ..... inner layer of semi-conducting material
3 ..... core insulation of cross-linked polyethylene
4 ..... outer layer of semi-conducting material
5 ..... screen of copper wires
6 ..... outer sheath of polyvinylchloride (PVC), red
Standards:
DIN VDE 0276-620
HD 620 S1: 1996
DIN EN 60228 class 2 (construction)
Technical data:
Test voltage | 6 / 10 kV | [kV] | 21 / 5 min. |
12 / 20 kV | [kV] | 42 / 5 min. | |
18 / 30 kV | [kV] | 63 / 5 min. | |
Temperature range | in motion | -5°C till +70°C | |
fixed | -20°C till +70°C | ||
Operating temperature | short circuit | °C | 250 |
Short circuit time | max. | [sec] | 5 |
Bending radius | min. | x diameter | 15 |
Flammability | standard | EN 60332-1-2 |
Number of cores and nominal cross section mm2 | Copper figure kg/km | Overall diameter appr. mm | Overall diameter max. value appr. mm | Weight appr. kg/km | Current carrying capacity ground A | Current carrying capacity air A | ||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
1 x 35 RM/16 | 540,0 | 27 | 32 | 1.100,0 | 189 | 200 | ||||||
1 x 50 RM/16 | 690,0 | 28 | 33 | 1.250,0 | 222 | 239 | ||||||
1 x 70 RM/16 | 890,0 | 30 | 35 | 1.450,0 | 271 | 297 | ||||||
1 x 95 RM/16 | 1.140,0 | 31 | 36 | 1.750,0 | 323 | 361 | ||||||
1 x 120 RM/16 | 1.390,0 | 33 | 38 | 2.050,0 | 367 | 416 | ||||||
1 x 150 RM/25 | 1.795,0 | 34 | 39 | 2.400,0 | 409 | 470 | ||||||
1 x 185 RM/25 | 2.145,0 | 36 | 41 | 2.800,0 | 461 | 538 | ||||||
1 x 240 RM/25 | 2.695,0 | 39 | 44 | 3.400,0 | 532 | 634 | ||||||
1 x 300 RM/25 | 3.295,0 | 41 | 46 | 4.000,0 | 599 | 724 | ||||||
1 x 400 RM/35 | 4.410,0 | 44 | 49 | 4.950,0 | 671 | 829 | ||||||
1 x 500 RM/35 | 5.410,0 | 47 | 52 | 6.050,0 | 754 | 953 |