NA2XSY (12 / 20 kV)

NA2XSY (12 / 20 kV)

XLPE Insulated Single-Core Cable with PVC Outer Sheath

Application:

To be laid directly in ground, outdoors, indoors and in cable ducts.

Construction:

1 ..... stranded (RM) aluminium wires
2 ..... inner layer of semi-conducting material
3 ..... core insulation of cross-linked polyethylene
4 ..... outer layer of semi-conducting material
5 ..... screen of copper wires
6 ..... outer sheath of polyvinylchloride (PVC), red

Standards:

DIN VDE0276-620
HD 620 S1: 1996
DIN EN 60228 class 2 (construction)

Technical data:

Test voltage 6 / 10 kV[kV]21 / 5 min.
12 / 20 kV[kV]42 / 5 min.
18 / 30 kV[kV]63 / 5 min.
Temperature rangein motion -5°C till +70°C
fixed-20°C till +70°C
Operating temperatureshort circuit°C250
Short circuit timemax.[sec]5
Bending radiusmin.x diameter15
FlammabilitystandardEN 60332-1-2
Number of cores and
nominal cross section

mm2
Aluminium
figure

kg/km
Copper
figure

kg/km
Overall
diameter
appr.
mm
Overall
diameter
max. value
appr. mm
Weight

appr.
kg/km
Current
carrying
capacity ground
A
Current
carrying
capacity air
A
1 x 50 RM/16147,01902833950,0172185
1 x 70 RM/16206,019030351.050,0210231
1 x 95 RM/16279,019031361.150,0251280
1 x 120 RM/16353,019033381.300,0285323
1 x 150 RM/25441,029534391.500,0319366
1 x 185 RM/25544,029536411.650,0361420
1 x 240 RM/25706,029539441.850,0417496
1 x 300 RM/25882,029541462.100,0471569
1 x 400 RM/351.176,041044492.550,0535660
* trefoil touching arrangement
This website uses cookies to provide services, personalize ads, and analyzing visitor. By using this site you agree. More informations