NA2XSY (12 / 20 kV)
NA2XSY (12 / 20 kV)
XLPE Insulated Single-Core Cable with PVC Outer Sheath
Application:
To be laid directly in ground, outdoors, indoors and in cable ducts.
Construction:
1 ..... stranded (RM) aluminium wires
2 ..... inner layer of semi-conducting material
3 ..... core insulation of cross-linked polyethylene
4 ..... outer layer of semi-conducting material
5 ..... screen of copper wires
6 ..... outer sheath of polyvinylchloride (PVC), red
Standards:
DIN VDE0276-620
HD 620 S1: 1996
DIN EN 60228 class 2 (construction)
Technical data:
Test voltage | 6 / 10 kV | [kV] | 21 / 5 min. |
12 / 20 kV | [kV] | 42 / 5 min. | |
18 / 30 kV | [kV] | 63 / 5 min. | |
Temperature range | in motion | -5°C till +70°C | |
fixed | -20°C till +70°C | ||
Operating temperature | short circuit | °C | 250 |
Short circuit time | max. | [sec] | 5 |
Bending radius | min. | x diameter | 15 |
Flammability | standard | EN 60332-1-2 |
Number of cores and nominal cross section mm2 | Aluminium figure kg/km | Copper figure kg/km | Overall diameter appr. mm | Overall diameter max. value appr. mm | Weight appr. kg/km | Current carrying capacity ground A | Current carrying capacity air A | |||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
1 x 50 RM/16 | 147,0 | 190 | 28 | 33 | 950,0 | 172 | 185 | |||||||
1 x 70 RM/16 | 206,0 | 190 | 30 | 35 | 1.050,0 | 210 | 231 | |||||||
1 x 95 RM/16 | 279,0 | 190 | 31 | 36 | 1.150,0 | 251 | 280 | |||||||
1 x 120 RM/16 | 353,0 | 190 | 33 | 38 | 1.300,0 | 285 | 323 | |||||||
1 x 150 RM/25 | 441,0 | 295 | 34 | 39 | 1.500,0 | 319 | 366 | |||||||
1 x 185 RM/25 | 544,0 | 295 | 36 | 41 | 1.650,0 | 361 | 420 | |||||||
1 x 240 RM/25 | 706,0 | 295 | 39 | 44 | 1.850,0 | 417 | 496 | |||||||
1 x 300 RM/25 | 882,0 | 295 | 41 | 46 | 2.100,0 | 471 | 569 | |||||||
1 x 400 RM/35 | 1.176,0 | 410 | 44 | 49 | 2.550,0 | 535 | 660 |