NA2XS(F)2Y (6 / 10 kV)

NA2XS(F)2Y (6 / 10 kV)

Single-Core XLPE Insulated Cable with PE Outer Sheath, longitudinally watertight

Application:

To be laid directly in ground, outdoors, indoors and in cable ducts.

Construction:

1 ..... stranded (RM) aluminium wires
2 ..... inner layer of semi-conducting material
3 ..... core insulation of cross-linked polyethylene
4 ..... outer layer of semi-conducting material
5 ..... swellable tape
6 ..... screen of copper wires
7 ..... anti-twist tape
8 ..... outer sheath of polyethylene (PE), black

Standards:

DIN VDE 0276-620
HD 620 S1: 1996
DIN EN 60228 class 2 (construction)

Technical data:

Test voltage 6 / 10 kV[kV]21 / 5 min.
12 / 20 kV[kV]42 / 5 min.
18 / 30 kV[kV]63 / 5 min.
Temperature rangein motion -5°C till +90°C
fixed-20°C till +90°C
Operating temperatureshort circuit°C250
Short circuit timemax.[sec]5
Bending radiusmin.x diameter15
FlammabilitystandardEN 60332-1-2
Number of cores and
nominal cross section

mm2
Aluminium
figure

kg/km
Copper
figure

kg/km
Overall
diameter
appr.
mm
Overall
diameter
max. value
appr. mm
Weight

appr.
kg/km
Current
carrying
capacity ground
A
Current
carrying
capacity air
A
1 x 50 RM/16147,01902429670,0171183
1 x 70 RM/16206,01902631770,0209226
1 x 95 RM/16279,01902732880,0248278
1 x 120 RM/16353,01902934950,0283321
1 x 150 RM/25441,029530351.150,0315364
1 x 185 RM/25544,029532371.250,0357418
1 x 240 RM/25706,029534391.500,0413494
1 x 300 RM/25882,029536411.700,0466568
1 x 400 RM/351.176,041040452.100,0529660
1 x 500 RM/351.479,041043482.450,0602767
* trefoil touching arrangement
This website uses cookies to provide services, personalize ads, and analyzing visitor. By using this site you agree. More informations