N2XSY (18 / 30 kV)
N2XSY (18 / 30 kV)
XLPE Insulated Single-Core Cable with PVC Outer Sheath
Application:
To be laid directly in ground, outdoors, indoors and in cable ducts.
Construction:
1 ..... stranded (RM) bare copper
2 ..... inner layer of semi-conducting material
3 ..... core insulation of cross-linked polyethylene
4 ..... outer layer of semi-conducting material
5 ..... screen of copper wires
6 ..... outer sheath of polyvinylchloride (PVC), red
Standards:
DIN VDE 0276-620
HD 620 S1: 1996
DIN EN 60228 class 2 (construction)
Technical data:
Test voltage | 6 / 10 kV | [kV] | 21 / 5 min. |
12 / 20 kV | [kV] | 42 / 5 min. | |
18 / 30 kV | [kV] | 63 / 5 min. | |
Temperature range | in motion | -5°C till +70°C | |
fixed | -20°C till +70°C | ||
Operating temperature | short circuit | °C | 250 |
Short circuit time | max. | [sec] | 5 |
Bending radius | min. | x diameter | 15 |
Flammability | standard | EN 60332-1-2 |
Number of cores and nominal cross section mm2 | Copper figure kg/km | Overall diameter appr. mm | Overall diameter max. value appr. mm | Weight appr. kg/km | Current carrying capacity ground A | Current carrying capacity air A | ||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
1 x 50 RM/16 | 690,0 | 33 | 38 | 1.450,0 | 225 | 241 | ||||||
1 x 70 RM/16 | 890,0 | 35 | 40 | 1.700,0 | 274 | 299 | ||||||
1 x 95 RM/16 | 1.140,0 | 36 | 41 | 2.050,0 | 327 | 363 | ||||||
1 x 120 RM/16 | 1.390,0 | 38 | 43 | 2.300,0 | 371 | 418 | ||||||
1 x 150 RM/25 | 1.795,0 | 39 | 44 | 2.700,0 | 414 | 472 | ||||||
1 x 185 RM/25 | 2.145,0 | 41 | 46 | 3.100,0 | 466 | 539 | ||||||
1 x 240 RM/25 | 2.695,0 | 43 | 48 | 3.700,0 | 539 | 635 | ||||||
1 x 300 RM/25 | 3.295,0 | 46 | 351 | 4.350,0 | 606 | 725 | ||||||
1 x 400 RM/35 | 4.410,0 | 49 | 54 | 5.300,0 | 680 | 831 | ||||||
1 x 500 RM/35 | 5.410,0 | 52 | 57 | 6.450,0 | 765 | 953 |