N2XSEY (6 / 10 kV)

N2XSEY (6 / 10 kV)

Three-Core XLPE Insulation Cable with PVC Outer Sheath

Application:

To be laid directly in ground, water, outdoors, indoors and in cable ducts e.g. in industrial and switchboard plants.

Construction:

1 ..... stranded bare copper
2 ..... inner layer of semi-conducting material
3 ..... core insulation of cross-linked polyethylene
4 ..... outer layer of semi-conducting material
5 ..... semi-conducting tape
6 ..... screen of copper wires
7 ..... inner covering over laid-up cores
8 ..... outer sheath of polyvinylchloride (PVC), red

Information:

short circuit temperature at core (max. 5 sec.)
<=300 mm² --> 160°C
>300 mm² --> 140°C

Standards:

DIN VDE 0276-620
HD 620 S1: 1996
IEC 60502
DIN EN 60228 class 2 (construction)

Technical data:

Nominal voltage Uo/U[V]6000 / 10000 volt
Test voltage[V]AC21000
Temperature rangein motion -5°C till +70°C
fixed-20°C till +70°C
Operating temperatureshort circuit°C250
Short circuit timemax.[sec]5
Bending radiusmin.x diameter15
FlammabilitystandardEN 60332-1-2
Number of cores and
nominal cross section

mm2
Copper
figure

kg/km
Overall
diameter
appr.
mm
Weight

appr.
kg/km
Current
carrying
capacity ground
A
Current
carrying
capacity air
A
3 x 35 RM/161.260,0492.600,0213213
3 x 50 RM/161.690,0512.900,0220236
3 x 70 RM/162.290,0553.350,0261265
3 x 95 RM/163.119,0584.200,0312322
3 x 120 RM/163.790,0625.050,0355370
3 x 150 RM/254.795,0666.000,0399420
3 x 185 RM/255.845,0697.200,0451481
3 x 240 RM/257.495,0759.000,0523566