N07V3V3-F
N07V3V3-F
PVC Building Site Cabl
Application:
This cable is suitable for connecting electrical equipment particularly on building sites. It is used in dry and damp locations, outdoors and in areas with explosion hazard.
Construction:
1 ..... fine-stranded bare copper
2 ..... core insulation of cold-resistant polyvinylchloride(PVC)
3 ..... outer sheath of cold-resistant polyvinylchloride (PVC), yellow
Information:
Cable may be used only in Austria as a building site cable.
Standards:
ÖVE / Östandard E8241-55
DIN EN 60228 class 5 (construction)
HD 308 S2 (core identification)
Technical data:
Nominal voltage Uo/U | [V] | 450 / 750 volt | |
Test voltage | [V]AC | 2500 | |
Temperature range | in motion | -35°C till +70°C | |
Operating temperature | short circuit | °C | 160 |
Short circuit time | max. | [sec] | 5 |
Bending radius | min. | x diameter | 6 |
Flammability | standard | EN 60332-1-2 |
Number of cores and nominal cross section mm2 | Copper figure kg/km | Cond. construction (appr. value) mm | Overall diameter appr. mm | Weight appr. kg/km | |||
---|---|---|---|---|---|---|---|
2 X 1,5 | 30 | 30 x 0,26 | 9,0 | 85,0 | |||
3 G 1,5 | 45 | 30 x 0,26 | 10,5 | 132,0 | |||
4 G 1,5 | 60 | 30 x 0,26 | 11,6 | 161,0 | |||
5 G 1,5 | 75 | 30 x 0,26 | 12,8 | 185,0 | |||
3 G 2,5 | 75 | 50 x 0,26 | 12,4 | 197,0 | |||
4 G 2,5 | 100 | 50 x 0,26 | 13,8 | 238,0 | |||
5 G 2,5 | 125 | 50 x 0,26 | 15,2 | 291,0 | |||
5 G 4 | 200 | 56 x 0,31 | 17,8 | 420,0 | |||
5 G 6 | 300 | 84 x 0,31 | 19,9 | 598,0 | |||
5 G 10 | 500 | 80 x 0,41 | 26,0 | 1.051,0 | |||
5 G 16 | 800 | 128 x 0,41 | 29,9 | 1.442,0 |