E-Y2Y

E-Y2Y

PVC Insulated Heavy Current Cable with Copper Conductor and PE Outer Sheath

Application:

This power cable is suitable for fixed installations, preferably in cable ducts, indoors, outdoors, in water or underground if no mechanical damage is to be Expected.

Construction:

1 ..... solid (RE) or stranded (RM/SM) bare copper
2 ..... core insulation of polyvinylchloride (PVC)
3 ..... PVC core covering or taping
4 ..... outer sheath of polyethylene (PE), black, Shore-hardness >55

Standards:

ÖVE K 23 a K 603
HD 603 S1:1994 + A2:2003
DIN EN 60228 class 1 and 2 (construction)
HD 308 S2 (core identification)

Technical data:

Nominal voltage Uo/U[V]600 / 1000 volt
Test voltage[V]AC4000
Temperature rangein motion -5°C till +70°C
one time / fixed-20°C till +70°C
Operating temperatureshort circuit°C160
Short circuit timemax.[sec]5
Bending radiussingle-core stylex diameter15
multi-core stylex diameter12
FlammabilitystandardEN 60332-1-2
Number of cores and
nominal cross section

mm2
Copper
figure

kg/km
Overall
diameter
appr.
mm
Weight

appr.
kg/km
Current
carrying
capacity ground
A
Current
carrying
capacity air
A
4 x 6 RE240,015570,05843
4 x 10 RE400,020775,07859
4 x 10 RM400,020775,07859
4 x 16 RE640,0211.050,010178
4 x 16 RM640,0221.100,010178
4 x 25 RM1.000,0251.632,0132105
4 x 35 SM1.400,0271.959,0159129
4 x 50 SM2.000,0322.595,0188157
5 x 6 RE300,017672,05843
5 x 10 RE500,021921,07859
* The current carrying capacity of the cables depends on the number of cores loaded (see DIN VDE 0276-627)