E-AY2Y
E-AY2Y
PVC Insulated Heavy Current Cable with Aluminium Conductor and PE Outer Sheath
Application:
This power cable is suitable for fixed installations in cable ducts outdoors, in water or underground if no mechanical damage is to be expected.
Construction:
1 ..... solid (RE/SE) or stranded (RM/SM) aluminium wire
2 ..... core insulation of polyvinylchloride (PVC)
3 ..... PVC core covering or taping
4 ..... outer sheath of polyethylene (PE), black, Shore-hardness HD
Standards:
ÖVE K 23 a K 603
HD 603 S1
DIN EN 60228 class 1 and 2 (construction)
HD 308 S2 (core identification)
Technical data:
Nominal voltage Uo/U | [V] | 600 / 1000 volt | |
Test voltage | [V]AC | 4000 | |
Temperature range | in motion | -5°C till +70°C | |
one time / fixed | -20°C till +70°C | ||
Operating temperature | short circuit | °C | 160 |
Bending radius | single-core style | x diameter | 15 |
multi-core style | x diameter | 12 | |
Short circuit time | max. | [sec] | 5 |
Number of cores and nominal cross section mm2 | Aluminium figure kg/km | Overall diameter appr. mm | Weight appr. kg/km | Current carrying capacity ground A | Current carrying capacity air A | |||||
---|---|---|---|---|---|---|---|---|---|---|
1 x 120 RM | 353,0 | 20 | 525,0 | 389 | 302 | |||||
3 x 240/120 SM | 2.470,0 | 55 | 3.994,0 | 364 | 338 | |||||
4 x 25 RE | 294,0 | 24 | 769,0 | 102 | 82 | |||||
4 x 50 SE | 588,0 | 28 | 1.093,0 | 144 | 119 | |||||
4 x 95 SE | 1.117,0 | 37 | 1.930,0 | 215 | 186 | |||||
4 x 150 SE | 1.764,0 | 45 | 2.822,0 | 275 | 246 | |||||
4 x 25 RM | 294,0 | 24 | 769,0 | 102 | 82 | |||||
4 x 35 SM | 412,0 | 25 | 868,0 | 123 | 100 | |||||
4 x 50 SM | 588,0 | 28 | 1.091,0 | 144 | 119 | |||||
4 x 95 SM | 1.117,0 | 37 | 1.930,0 | 215 | 186 | |||||
4 x 150 SM | 1.764,0 | 43 | 2.449,0 | 275 | 246 | |||||
4 x 185 SM | 2.176,0 | 48 | 3.075,0 | 313 | 285 | |||||
4 x 240 SM | 2.822,0 | 57 | 4.509,0 | 364 | 338 |