E-A2Y

E-A2Y

PE Insulated Overhead Line

Application:

This overhead line is particularly suited as a roof pylon cable outdoors, but not Underground.

Construction:

1 ..... stranded compacted aluminium wires
2 ..... outer sheath of polyethylene (PE), black

Standards:

ÖVE / Östandard E8200-626
HD 626 S1

Technical data:

Nominal voltage Uo/U[V]600 / 1000 volt
Test voltage[V]AC3500
Temperature rangein motion-20°C till +90°C
Operating temperatureshort circuit°C120
Short circuit timemax.[sec]5
Bending radiusin motion x diameter18
Number of cores and
nominal cross section

mm2
Aluminium
figure

kg/km
Max. overall
diameter
of insulation
mm
Overall
diameter
appr.
kg/km
Weight

appr.
kg/km
Current
carrying
capacity air
A
2 x 25 RM147,0917,4210,080
4 x 25 RM294,0921,0420,080
4 x 50 RM588,01327,5740,0125
4 x 70 RM823,01431,91.000,0160
4 x 95 RM1.117,01636,71.350,0185