SiF / GL
SiF / GL
Silicone Insulated Wire with Fibreglass Braiding
Application:
This wire is well suited for internal wiring in lamps, instruments, control panels and distributors. It is used for high mechanical stress, as the fibreglass braiding protects the silicone insulation from mechanical damages. It is halogen-free and heat resistant.
Construction:
1 ..... fine-stranded tinned or bare copper
2 ..... core insulation of silicone (2GI1)
3 ..... impregnated fibreglass braiding
Standards:
DIN EN 60228 class 5 (construction)
Technical data:
Nominal voltage Uo/U | [V] | 300 / 500 volt | |
Test voltage | [V]AC | 2000 | |
Temperature range | in motion | -60°C till +180°C | |
temporary resilient | +250°C | ||
Flammability | standard | EN 60332-1-2 |
Number of cores and nominal cross section mm2 | Colours | Copper figure kg/km | Cond. construction (appr. value) mm | Overall diameter appr. mm | Weight appr. kg/km | ||||
---|---|---|---|---|---|---|---|---|---|
0,75 | ws | 7,5 | 24 x 0,21 | 2,7 | 15,0 | ||||
1,00 | ws | 10,0 | 32 x 0,21 | 2,8 | 18,0 | ||||
1,50 | ws | 15,0 | 30 x 0,26 | 3,3 | 26,0 | ||||
2,50 | ws | 25,0 | 50 x 0,26 | 3,9 | 38,0 | ||||
4,00 | ws | 40,0 | 56 x 0,31 | 4,5 | 55,0 | ||||
6,00 | ws | 60,0 | 84 x 0,31 | 5,2 | 76,0 | ||||
10,00 | ws | 100,0 | 80 x 0,41 | 7,3 | 136,0 | ||||
16,00 | ws | 160,0 | 128 x 0,41 | 8,3 | 200,0 | ||||
25,00 | ws | 250,0 | 200 x 0,41 | 10,2 | 311,0 | ||||
35,00 | ws | 350,0 | 280 x 0,41 | 11,4 | 412,0 | ||||
50,00 | ws | 500,0 | 400 x 0,41 | 14,1 | 583,0 | ||||
70,00 | ws | 700,0 | 356 x 0,51 | 16,1 | 798,0 | ||||
95,00 | ws | 950,0 | 495 x 0,51 | 18,5 | 1.073,0 | ||||
120,00 | ws | 1,200,0 | 614 x 0,51 | 20,0 | 1.329,0 |