H07BQ-F

H07BQ-F

Polyurethane Building Site Cable with Rubber Insulated Conductors

Application:

This termination and connection cable with high mechanical stress-resistance can be used in dry, damp or wet rooms as well as in the open-air. It is ideal for application in industrial plants, building sites, in fact everywhere where extreme wear and tear resistance is required and where the cable is subjected to hard utilisation.

Construction:

1 ..... fine-stranded tinned or bare copper
2 ..... core insulation of a rubber compound (EL6)
3 ..... outer sheath of polyurethane (PUR), orang

Information:

with or without inner sheath available

Standards:

DIN VDE 0282-10
HD 22.10 S1+A1
DIN EN 60228 class 5 (construction)
HD 308 S2 (core identification)

Technical data:

Nominal voltage Uo/U[V]450 / 750 volt
Test voltage[V]AC2500
Temperature rangein motion-40°C till +90°C
Operating temperatureshort circuit°C200
Short circuit timemax.[sec]5
Bending radiusone time / fixedx diameter4
in motion x diameter5
Oil-resistantstandardEN 60811-2-1
FlammabilitystandardEN 60332-1-2
Number of cores and
nominal cross section

mm2
Copper
figure

kg/km
Cond.
construction
(appr. value)
mm
Overall
diameter
appr.
mm
Weight

appr.
kg/km
2 X 1,530,030 x 0,268,888,0
3 G 1,545,030 x 0,269,3110,0
4 G 1,560,030 x 0,2610,3140,0
5 G 1,575,030 x 0,2611,2169,0
7 G 1,5105,030 x 0,2614,0291,0
3 G 2,575,050 x 0,2611,0163,0
4 G 2,5100,050 x 0,2612,2208,0
5 G 2,5125,050 x 0,2613,5257,0
7 G 2,5175,050 x 0,2616,5431,0
4 G 4160,056 x 0,3114,0293,0
5 G 4200,056 x 0,3115,6365,0
5 G 6300,084 x 0,3117,6504,0
5 G 10500,080 x 0,4123,2962,0
5 G 16800,0128 x 0,4127,11.379,0
5 G 251.250,0200 x 0,4133,32.169,0
7 G 1,5105,030 x 0,2614,0291,0
7 G 2,5175,050 x 0,2616,5431,0
12 G 1,5180,030 x 0,2618,0446,0
12 G 2,5300,050 x 0,2621,0641,0
This website uses cookies to provide services, personalize ads, and analyzing visitor. By using this site you agree. More informations