YSLCY Intrinsically Safe

YSLCY EB

PVC Control Cable for Intrinsically Safe Circuits with Copper Braiding and Blue Outer Sheath

Application:

For dry, humid and wet locations as well as areas with explosion hazard, but not in the open-air. To be used as an MSR cable for the application in intrinsically safe circuits. The copper braiding optimises protection against external electrical and magnetic interferences. The cable is suitable for medium-level mechanical stress.

Construction:

1 ..... fine-stranded bare copper
2 ..... core insulation of polyvinylchloride (PVC)
3 ..... braiding of tinned copper wires
4 ..... outer sheath of polyvinylchloride (PVC), blue, increased oil resistant

Information:

Capacity:
core / core: ca. 150 nF/km
core / screen: ca. 200 nF/km
Inductivity: approx. 0,65 mH/km

Standards:

adapted to DIN VDE 0281
DIN EN 60228 class 5 (construction)
core identification JZ: 1 core green/yellow, other cores black with figures
core identification OZ: every core black with figure

Technical data:

Nominal voltage Uo/U[V]300 / 500 volt
Test voltage[V]AC2000
Temperature rangein motion -5°C till +70°C
one time / fixed-30°C till +70°C
Operating temperatureshort circuit°C150
Short circuit timemax.[sec]5
Bending radiusone time / fixedx diameter10
in motion x diameter20
FlammabilitystandardEN 60332-1-2
Number of cores and
nominal cross section

mm2
Copper
figure

kg/km
Cond.
construction
(appr. value)
mm
Overall
diameter
appr.
mm
Weight

appr.
kg/km
2 x 0,754324 x 0,216,256
3 x 0,755224 x 0,216,570
4 x 0,756124 x 0,217,096
5 x 0,757224 x 0,217,8157
7 x 0,758924 x 0,218,4168
12 x 0,7513824 x 0,2110,9231
18 x 0,7521124 x 0,2112,8314
25 x 0,7528024 x 0,2115,2434
2 x 1,56530 x 0,267,197
3 x 1,58230 x 0,267,6124
4 x 1,510030 x 0,268,2166
5 x 1,511930 x 0,269,0192
7 x 1,515430 x 0,269,8245
This website uses cookies to provide services, personalize ads, and analyzing visitor. By using this site you agree. More informations