YSL11Y

YSL11Y

PUR Control Cable

Application:

Used as energy or connecting cable, as measuring, checking and control cable in machine tool manufacturing, plant engineering and on assembly lines and production lines to meet stringent safety requirements. Suitable for fixed installation or flexible applications with unrestricted mobility without forced movement control and without exposure to tensile load. Installation in dry and moist rooms.

Construction:

1 ..... fine-stranded bare copper
2 ..... core insulation of polyvinylchloride (PVC)
3 ..... outer sheath of polyurethane (PUR), grey, oil resistant

Standards:

adapted to DIN VDE 0281
DIN EN 60228 class 5 (construction)
core identification JZ: 1 core green/yellow, other cores black with figures
core identification OZ: every core black with figures

Technical data:

Nominal voltage Uo/U[V]300 / 500 volt
Test voltage[V]AC3000
Temperature rangein motion -5°C till +70°C
one time / fixed-40°C till +70°C
Bending radiusone time / fixedx diameter6
in motion x diameter20
FlammabilitystandardEN 60332-1-2
Number of cores and
nominal cross section

mm2
Copper
figure

kg/km
Cond.
construction
(appr. value)
mm
Overall
diameter
appr.
mm
Weight

appr.
kg/km
2 x 0,7515,024 x 0,215,443
3 x 0,7522,524 x 0,215,761
4 x 0,7530,024 x 0,216,275
5 x 0,7537,524 x 0,216,7100
7 x 0,7552,524 x 0,217,3125
2 x 120,032 x 0,215,757
3 x 130,032 x 0,216,080
4 x 140,032 x 0,216,5106
5 x 150,032 x 0,217,1123
7 x 170,032 x 0,218,0149
2 x 1,530,030 x 0,266,3100
3 x 1,545,030 x 0,266,7110
4 x 1,560,030 x 0,267,2125
5 x 1,575,030 x 0,268,1145
7 x 1,5105,030 x 0,268,9195
3 x 2,575,048 x 0,268,1170
4 x 2,5100,048 x 0,268,9180
5 x 2,5125,048 x 0,2610,0190
7 x 2,5175,048 x 0,2611,1280
This website uses cookies to provide services, personalize ads, and analyzing visitor. By using this site you agree. More informations