E-YCY

E-YCY

PVC Insulated Cable with Concentric Conductor Screen Cross Section 16 mm2

Application:

In dry, humid and wet locations, cable ducts, outdoors, underground and in Water.

Construction:

1 ..... solid (RE) or stranded (RM/SM) bare copper
2 ..... core insulation of polyvinylchloride (PVC)
3 ..... PVC core covering or taping
4 ..... concentric conductor of copper wires and copper tape
5 ..... outer sheath of polyvinylchloride (PVC), black

Standards:

ÖVE K23 a K 603
HD 603.S1
DIN EN 60228 Class 1 (construction)
HD 308 S2 (core identification)

Technical data:

Nominal voltage Uo/U[V]600 / 1000 volt
Test voltage[V]AC4000
Temperature rangein motion -5°C till +70°C
fixed-20°C till +70°C
Operating temperatureshort circuit°C160
Short circuit timemax.[sec]5
Bending radiusone time / fixed x diameter12
in motionx diameter15
FlammabilitystandardEN 60332-1-2
Number of cores and
nominal cross section

mm2
Copper
figure

kg/km
Overall
diameter
appr.
mm
Weight

appr.
kg/km
Current
carrying
capacity ground
A
Current
carrying
capacity air
A
4 x 1,5 RE/ 1625015260,02618
7 x 1,5 RE/ 1629517540,000
10 x 1,5 RE/ 1634020660,000
12 x 1,5 RE/ 1637020700,000
14 x 1,5 RE/ 1640021750,000
19 x 1,5 RE/ 1647523900,000
24 x 1,5 RE/ 16550271.110,000
30 x 1,5 RE/ 16640281.260,000
4 x 2,5 RE/ 1629016330,03425
5 x 2,5 RE/ 1631517580,000
7 x 2,5 RE/ 1636518630,000
10 x 2,5 RE/ 1644021800,000
12 x 2,5 RE/ 1649022890,000
14 x 2,5 RE/ 1654023980,000
19 x 2,5 RE/ 16665261.180,000
24 x 2,5 RE/ 16790291.450,000
30 x 2,5 RE/ 16940301.630,000
2 x 4 RE/ 1627016510,04434
4 x 4 RE/ 1635018630,04434
5 x 4 RE/ 1639019730,000
7 x 4 RE/ 1647024950,000
4 x 6 RE/ 1643019750,05643
5 x 6 RE/ 1649021860,000
4 x 10 RE/ 1659022970,07560
5 x 10 RE/ 16690251.200,000
5 x 16 RE/ 16990271.475,000
* The current carrying capacity of the cables depends on the number of cores loaded (see DIN VDE 0276-627)